Liquid Cooled Rack-Scale Solution NVIDIA GB300 NVL72 with 72 NVIDIA B300 GPUs and 36 Grace CPUs
Engineered for professionals who demand the best in performance, security, and design.
72 NVIDIA B300 GPUs via NVIDIA GB300 Grace Blackwell Ultra Superchips, with up to 21TB HBM3e GPU memory
36 NVIDIA Grace CPUs with up to 17TB LPDDR5X system memory
9 NVLink Switches connecting all 72 GPUs with 1.8TB/s GPU-to-GPU interconnect
NVIDIA Quantum-X800 InfiniBand or Spectrum-X Ethernet with ConnectX®-8 SuperNICs, plus BlueField-3 DPUs for in-band management
Up to 144 E1.S PCIe 5.0 drive bays across 18 1U compute nodes
In-rack 250kW CDU standard, with in-row (up to 1.8MW) and L2A sidecar CDU options
8x 1U 33kW power shelves (6x 5.5kW PSUs each), 132kW total
Fully integrated 48U rack-scale solution with 18 compute nodes
Full specifications for the model
| SKU | SRS-GB300-NVL72 |
|---|---|
| Gpus | 72 NVIDIA B300 GPUs via NVIDIA GB300 Grace Blackwell Ultra Superchips |
| Cpus | 36 NVIDIA Grace CPUs via NVIDIA GB300 Grace Blackwell Ultra Superchips |
| Gpu Memory | Up to 21 TB HBM3e |
| System Memory | Up to 17 TB LPDDR5X |
| Storage | Up to 144 E1.S PCIe 5.0 drive bays |
| Nodes | 18x 1U ARS-121GL-NB3 |
| Networking | 9x NVLink Switch, 4-ports per compute tray connecting 72 GPUs to provide 1.8TB/s GPU-to-GPU interconnect |
| Power | 8x 1U 33kW (6x 5.5kW PSUs), total power 132kW |
| Liquid Cooling | 1x in-rack Supermicro 250kW capacity CDU with redundant PSU and dual hot-swap pumps |
| Rack Enclosure | 48U, 19”-width |
| Dimensions | W 600 x D 1068 x H 2236 |
| Compute Fabric | NVIDIA Quantum-X800 InfiniBand or NVIDIA Spectrum-X Ethernet with integrated NVIDIA ConnectX®-8 SuperNICs for up to 800Gb/s compute fabric |
| In Band Network | Up to 200Gb/s In-Band Management speeds with NVIDIA BlueField-3 DPUs |
| Out Of Band Network | 1G/10G Ethernet out-of-band management |
| Liquid Cooling Options | In-Rack CDU: Up to 250 kW capacity CDU with N+1 redundant pumps In-Row CDU: Up to 1.8 MW capacity CDU with N+1 redundant pumps (supports up to 8 racks) L2A Sidecar CDU: Up to 200 kW capacity CDU with N+1 redundant pumps (no facility water required) |
Explore other configurations and models that might suit your needs.
Recommended
#ARS-121GL-NB2B-LCC
1U NVIDIA GB200 NVL4 system with quad 800G NVIDIA ConnectX®-8 or custom NICs, and up to 8 E1.S drives
Recommended
#ARS-511GD-NB-LCC
Super AI Station with NVIDIA GB300 Grace Blackwell Ultra Desktop Superchip
Recommended
#SYS-222GS-NB3OT-ALC
DP Intel 2 OU (OCP ORv3) Liquid-Cooled System with NVIDIA HGX B300 8-GPU (complete rack and onsite service are required)
Our team of experts is ready to help you find the perfect solution for your business needs. Get personalized advice and competitive quotes.